D1033Q
4 Ch, /Proximity Detector Repeater, Transistor Output, SIL 2 |
 |
|
|
|
|
| Learn more on Intrinsic Safety's basic principles, standards and directives |
|
|
|
|
|
 |
D2011M
Intrinsically Safe Analog - Temperature Multiplexer Expander for D2010M
|
|
|
| Code: |
D2011M |
|
| Type: |
Multiplexer (Show others) |
|
| Supply: |
Via D2010M |
|
| Channels: |
16 |
|
| Description: |
Multiplexer Units D2011M can be installed in the field, close to input sensors, for data aquisition from Hazardous Area. They are connected to D2010M Units to expand the acquiring capabilities.
The Units are primarily intended for Hazardous Area acquisition of low level
signals from Thermocouples, RTDs, mV or mA sources.
D2011M scans all enabled channels using state of the art solid state isolated
relays, and stores all data in a memory buffer, where they can be rapidly
accessed by the Modbus Gateway Unit D2050M.
Expander Units D2011M are connected to D2010M via 20 pole flat cable (up to 30 cm long).
All parameters are software configurable by serial commands
via D2050M Gateway Unit.
|
|
| Features: |
• Intrinsically Safe for installation in Zone 1, 2.
• Universal Inputs (mV, TC, RTD and mA) from Zone 0, 1, 2.
• 200 V input-to-input, and 500 V input to ground, isolation accepts
multiple grounded sensors.
• High Accuracy A/D Converter, 18 bits.
• 16 input channels.
• EMC according to EN50081-2, EN50082-2.
• ATEX approval.
• High Reliability, SMD components.
• High Density, 16 channels per unit.
• Software configuration.
• Simplified installation using standard DIN Rail mounting Units.
|
|
| Datasheet: |
| DTS0121 | D2011M PDF product datasheet |
 |
|
|
| Certifications: |
| CRT024 | D2000M Series Atex Certificate |
 |
| CRT020 | FM 3024643 (USA) & FM-C 3029921C (Canada) |
 |
|
|
| Instruction manual: |
| ISM0078 | PDF Instruction manual for D2011M |  | |
|