D1072D
2 Ch, Temp. Signal Conv, Dupl.-Select.-Adder-Subtract SIL 2
|
|
|
| Code: |
D1072D |
|
| Type: |
Temperature Converter (Show others) |
|
| Supply: |
24 Vdc |
|
| Field Device: |
|
|
| Channels: |
2 |
|
| Description: |
The D1072D converts two mV, RTD, TC, inputs from temperature sensors, or from Transmitting Potentiometers located in Hazardous Location, and repeats, with isolation, the two isolated signals to drive two independent Safe Area loads. Output Signals can be direct, duplicated, the sum or the difference of the two inputs, or the higher-lower selection of the two inputs. Automatic or manual Cold Junction or Line Resistance compensation are standard. All settings are easily programmable via software. Approved for Div. 2 installation.
One channel SIL 2 according to IEC 61508 and 61511 standards. |
|
| Hazardous Area: |
Input from TC with automatic cold junction compensation, 2,3,4 wire RTD, or Transmitter Potentiometer with burnout indication. |
|
| Safe Area: |
4-20 mA/0-20 mA or 1-5 V/0-5 V or 2-10 V/0-10 V output signal totally isolated from Input and Supply. |
|
| Function: |
2 channels I.S. input from millivolt, thermocouples or 3, 4 wire resistance
thermometers or transmitting potentiometers, provides 3 port isolation
(input/output/supply) and current or voltage output signal.
Duplicator, adder, subtractor, low/high selector.
The programmable RTD line resistance compensation allow use of 2 wire
RTDs or error compensation for 3-4 wire RTDs.
Cold Junction compensation can be automatic, with option 91, or fixed by
software setting. |
|
| Features: |
• One channel SIL 2 according to IEC 61508 and 61511 standards.
• High density with 2 independent channels.
• Fully software programmable.
• All temperature inputs (mV-TC-RTD-POT-Ω).
• mA or V output.
• Signal duplicator retaining i.a. approval.
• Signal selector (high-low) or adder or subtracter
• Automatic or Manual CJC.
• Resistance line compensation. |
|
| SIL rating: |
D1072D is suitable for SIL 2 applications according IEC61508 & IEC61511. PFD avg = 4.16 E-04; MTBF = 208 years; Please see our functional Safety manual for details. |
|
| Datasheet: |
| DTS0025 | D1072D PDF product datasheet |
 |
|
|
| Certifications: |
| CRT005 | UL & C-UL |
 |
| CRT008 | TCCExEE (Russia) |
 |
| CRT003 | ATEX DMT 01 ATEX E 042 X |
 |
| CRT009 | TCCExEE (Ukraine) |
 |
| CRT010 | Gosgortehnadzor (Russia) |
 |
| CRT011 | GOSSTANDARD (Russia) |
 |
| CRT012 | Gosnadzorohrantruda (Ukraine) |
 |
| CRT020 | FM 3024643 (USA) & FM-C 3029921C (Canada) |
 |
| CRT023 | DNV Certificate for Ships and Offshore Standards |
 |
| CRT032 | IECEx Certificate for D1000 Series |
 |
| CRT047 | IMQ 09 ATEX 013 X |
 |
|
|
| Application notes: |
| APN0005 | D1052-53, D1072-73 Signal Converter DIN Rail |  | | APN0006 | D1070, D1072, D1073 Signal Converter DIN Rail |  | | APN0007 | Universal AC Power Supply for Series D1000 |  | | APN0008 | D1072D /02 Temperature Converter DIN Rail |  | | APN0012 | D1070,D1072,D1073 Signal Converter DIN Rail |  | | APN0020 | D1072 /024 mV Isolator DIN Rail |  | |
|
| Instruction manual: |
| ISM0018 | PDF Instruction manual for D1072D |  | | ISM0062 | PDF Instruction manual for D1072D |  | |
|
| Various: |
|
|
| Software: |
| SWC1090 | D1000 and E1000 Software Configurator for Windows |  | |
|
| Accessories: |
| D1072D | 2 Ch, Temp. Signal Conv, Dupl.-Select.-Adder-Subtract SIL 2 | | D1072D/B | 2 Ch, Temp. Signal Conv, Dupl.-Select.-Adder-Subtract SIL 2 | | OPZ91 | Cold Junction Compensator Required for TC Inputs | | PPC1090 | Pocket Portable Configurator for D105* D106* D107* | | PPC1092 | D1000 Series Serial Adapter Configurator. | | USBADAPT | RS-232 to USB Adapter. | |
|
|
|
|
|