Select: Intrinsically safe equipment for Hazardous Locations
Home |  Products |  Contact us |  Help
MENU
Homepage
Products
SIL rating
Download
Software
Work with us
News
Intrinsic Safety
About us
Choosing GM
Reps/Distributors
Contacts
Help center
SEARCH
Product Selector
Product name:
Product category:
Free search:
RECENT
D1061S

Single Channel RS 422 / RS 485 Field Bus Isolating Repeater
WORLDWIDE
I.S. BASICS
 
Learn more on Intrinsic Safety's basic principles, standards and directives
D1060S PRODUCT DETAILS
  • D1060S


  • 1 Ch, Frequency-Pulse Converter, Repeater and Trip Amplifier
    Code: D1060S
    Type: Signal Converter and Trip Amplifier (Show others)
    Supply: 24 Vdc
    Field Device: Pick Up
    Channels: 1
    Description: The D1060S converts and repeats, with isolation, a low level frequency signal (0-50 Khz) from magnetic pick-up, contact, proximity, open-collector transistor or logic level sensor located in Hazardous Location, into a 0-20/4-20 mA current or voltage output signal to drive a Safe Area load. The pulse output can be direct or divided by a factor of 10 or it can be programmed as alarm function. One additional independent Alarm Trip Amplifier is also provided; total of two when using the pulse output as an alarm mode. Alarm energizes, or de-energizes an SPST opt coupled open-collector transistor for High, Low or Low-start-up alarm function. All settings are easily programmable via software. Approved for Div. 2 installation.
    Hazardous Area: Frequency input from magnetic pick-up, contact, proximity switch or logic level sensor.
    Safe Area: 4-20 mA/0-20 mA or 1-5 V/0-5 V or 2-10 V/0-10 V output signal totally isolated from Input and Supply plus frequency input repeater with open collector transistor plus independent set point with open collector transistor.
    Function: 1 channel I.S. input from frequency-pulse signals, provides 3 port isolation (input/output/supply) and current or voltage output signal. In addition it repeats the frequency input and provides one SPST transistor with adjustable Alarm Trip Point.
    Features: • Fully software programmable.
    • All frequency inputs (Pick/up-Prox-Swtc-TTL).
    • mA or V output.
    • Frequency repeater/divider.
    • Built-in trip amplifier.
    Datasheet:
    DTS0162 D1060S PDF product datasheet
    Certifications:
    CRT005UL & C-UL
    CRT008TCCExEE (Russia)
    CRT003ATEX DMT 01 ATEX E 042 X
    CRT009TCCExEE (Ukraine)
    CRT010Gosgortehnadzor (Russia)
    CRT011GOSSTANDARD (Russia)
    CRT012Gosnadzorohrantruda (Ukraine)
    CRT020FM 3024643 (USA) & FM-C 3029921C (Canada)
    CRT023DNV Certificate for Ships and Offshore Standards
    CRT032IECEx Certificate for D1000 Series
    CRT047IMQ 09 ATEX 013 X
    Application notes:
    APN0007Universal AC Power Supply for Series D1000
    Instruction manual:
    ISM0054PDF Instruction manual for D1060S
    ISM0062PDF Instruction manual for D1060S
    Various:
    main_catalog General Products and Company Catalog
    shortform_catalog Short Form Products Catalog
    Software:
    SWC1090D1000 and E1000 Software Configurator for Windows
    Accessories:
    D1060S1 Ch, Frequency-Pulse Converter, Repeater and Trip Amplifier
    D1060S/B1 Ch, Frequency-Pulse Converter, Repeater and Trip Amplifier
    PPC1090Pocket Portable Configurator for D105* D106* D107*
    PPC1092D1000 Series Serial Adapter Configurator.
    USBADAPTRS-232 to USB Adapter.
    « Previous: D1054SD1060SNext: D1061S »

    See also D1060S page at www.gmintsrl.com