D1022S
1 ch. Loop Powered Fire / Smoke Detector Interface
|
|
|
| Code: |
D1022S |
|
| Type: |
Analog Input (Show others) |
|
| Supply: |
Loop Powered |
|
| Field Device: |
|
|
| Channels: |
1 |
|
| Description: |
The D1022S is a loop-powered single channel isolated interface to be used with fire and smoke detectors located in hazardous areas, or with similar switched resistor systems requiring a wide output current range (from 1 to 40 mA) to operate properly. The triggering of a detector causes a corresponding change in the safe area circuit. The unit has reverse input polarity protection. This unit can also be used to drive an I/P located in Hazardous areas but with reduced accuracy (less or equal to 1%) |
|
| Hazardous Area: |
1 to 40 mA
V out = (Vin - 1.5) - (0.4 x Iout) for 6V < Vin < 23V
V out = 22 - (o.4 x Iout) for 23V < Vin < 30V
4-20 mA output on output load of 100 to 600 Ohm; Accuracy < 1% |
|
| Safe Area: |
1 to 40 mA
6 to 30 V |
|
| Function: |
1 channel Intrinsically Safe analog input for fire-smoke destector providing input-output isolation |
|
| Features: |
• Wide operating current range from 1 to 40 mA
• ATEX certification
• High Reliability
• 250 Vrms (Um) maximum voltage applied to the instruments associated with barrier |
|
| Datasheet: |
| DTS0195 | D1022S PDF product datasheet |
 |
|
|
| Certifications: |
| CRT003 | ATEX DMT 01 ATEX E 042 X |
 |
| CRT020 | FM 3024643 (USA) & FM-C 3029921C (Canada) |
 |
| CRT032 | IECEx Certificate for D1000 Series |
 |
| CRT047 | IMQ 09 ATEX 013 X |
 |
|
|
| Instruction manual: |
| ISM0077 | PDF Instruction manual for D1022S |  | |
|
| Various: |
|
|
|
|
|
|